If I have three identical inverters rated @ 3kwac, and 240VAC, on a residential system, (non-back up), what would be the best utility disconnect rating for this system?
Comments
Hi pathic,
You need to multiply the inverter output current with 1.25 to find the appropriate AC disconnect rating.
I attach the Long Beach, CA permit authority document that tells you how to calculate what you are looking for. It's also explained in NEC code book.
Comments
Hi pathic,
You need to multiply the inverter output current with 1.25 to find the appropriate AC disconnect rating.
I attach the Long Beach, CA permit authority document that tells you how to calculate what you are looking for. It's also explained in NEC code book.